MTXvD is designed to map the state and control all types of switches used in power facilities. Each device can be equipped with up to 4 cards with 15 binary inputs each (60 inputs in total) and up to 4 binary output cards (maximum 60 relay outputs).
Output cards with hybrid relays are available: with high-speed operate time < 0.1 ms and breaking current up to 3A @ 250VDC L/R = 20 ms and 6A @ 250VAC.
multi-processor digital measurement and decision-making system,
galvanic separation of individual inputs and outputs (analog and digital),
permanent control of the correctness of internal systems,
password-protected access to settings,
GPS receiver for autonomous time synchronization,
1PPS optical signal input for time synchronization,
time synchronization accuracy +/- 2 us,
time synchronization via NTP and 1PPS protocol, IEEE 1588v2 option,
GOOSE message handling in accordance with the IEC 61850-8-1 standard,
preview of binary input states,
two 100BASE-FX SFP ports enabling the use of a fiber optic link for GOOSE messages on the P-bus (process bus) in VLAN or redundant PRP mode, and two local 100BASE-T ports – engineering and PC link,
advanced Ethernet communication functions, including VLAN in accordance with IEEE802.1Q and PRP redundancy in accordance with EN 62439-3.
receiving multiple GOOSE messages with the ability to create logic, also using fast and powerful hybrid relays,
possibility of cooperation with station switches,
possibility of visualization, control and configuration via SAZ2000 software and/or CCDM ( Computers & Control Device Manager ).